  • 28.jpg

SF6 gas-insulated metal-enclosed switchgear


The UN7-72.5kV series gas-insulated metal-enclosed switchgear is suitable for the following locations:
· Inside offshore and onshore wind turbine towers connected to a 72.5 kV voltage grid
· 72.5kV voltage-rated grid-connected photovoltaic power generation systems, both offshore and onshore, installed outdoors as well as inside box-type substations.
· Outdoor and indoor transformer substations for offshore and onshore energy storage systems connected to a 72.5 kV voltage grid

Classification

Product Center


▎Product Features


· Safe and reliable
· Meets outdoor industrial and mining requirements, and adapts to both marine and land environmental conditions.
· Comprehensive solutions with flexible combinations
· On-site installation—no disassembly, no inflation, and no maintenance required.

 

▎Operating Environment Conditions


· For outdoor or indoor use;
· Altitude: ≤5000 m (If the operating altitude of the equipment exceeds 2000 m, this must be specifically noted);
· Ambient temperature: Maximum temperature +65℃, minimum temperature -40℃, average value within 48 hours ≤35℃;
· Environmental humidity: Suitable for all humid environments;
· Pollution degree: Level 4 pollution;
· Corrosion resistance class: Offshore C4H;
· Seismic resistance level: AG5 (horizontal acceleration 0.3g, vertical acceleration 0.15g);
· Electromagnetic interference: The amplitude of electromagnetic interference induced in the secondary system ≤ 1.6 kV;
· Installation environment: There should be no explosive or corrosive gases in the surrounding air, and the installation location should be free from frequent, severe vibrations or impacts.
· Note: If the operating environment conditions exceed those specified above, please consult with the company to arrange custom solutions.

 

 

▎Applicable Standards


· GB/T 7674-2020 Gas-insulated metal-enclosed switchgear with rated voltage of 72.5 kV and above
· IEC62271-203:2011 Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV
· IEC60694-2002 Common Technical Requirements for High-Voltage Switchgear and Control Equipment
· GB/T3906-2020 and IEC 62271-200:2011—3.6 kV to 40.5 kV AC metal-enclosed switchgear and control equipment
· Common technical requirements shared by GB/T 11022-2020 and IEC 62271-1:2017—Standard for High-Voltage Switchgear and Control Equipment
· GB/T1984-2014 and IEC 62271-100:2017 AC High-Voltage Circuit Breakers
· GB/T4208-2017 and IEC60529 Enclosure Protection Ratings (IP Codes)
· GB/T16927.1~2-2013 High-Voltage Test Techniques
· GB/T3309-1989 Mechanical Tests for High-Voltage Switchgear at Ambient Temperature
· GB/T 4473-2018 Synthetic Testing of High-Voltage AC Circuit Breakers
· GB/T5582-1993 Pollution Severity Levels for External Insulation of High-Voltage Power Equipment
· GB/T11023-2018 Test Method for Gas Sealing of Sulfur Hexafluoride in High-Voltage Switchgear
· DL/T402-2017 Technical Specifications for Ordering High-Voltage AC Circuit Breakers
· DL/T486-2021 Technical Specifications for Ordering High-Voltage AC Disconnect Switches and Earthing Switches
· DL/T403-2017 Technical Specifications for Ordering 12kV~40.5kV High-Voltage Vacuum Circuit Breakers
· DL/T404-2018 3.6kV~40.5kV AC Metal-Enclosed Switchgear and Control Equipment
· DL/T593-2016 Common Technical Requirements for High-Voltage Switchgear and Control Equipment Standards

 

 

▎Product Parameters


 

Name

Unit

Switchgear and Circuit Breaker Parameters

Rated voltage

kV

72.5

Rated frequency

Hertz

50

Rated current

A

630/1250

 

Rated insulation level

Power-frequency withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter)

kV

160

Power-frequency withstand voltage (isolated break)

kV

160+42

Power-frequency withstand voltage (auxiliary and control circuits)

kV

2

Lightning impulse withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter)

kV

380

Lightning Impulse Withstand Voltage (Isolation Break)

kV

350 + 60

Rated short-circuit breaking current

kA

31.5

Rated short-circuit breaking operations

Next

30

Rated short-circuit making current (main switch/fault-making earthing switch)

kA

80/80

Short-time withstand current and duration (main circuit + earthing switch, earthing connection)

kA/s

31.5/4, 27.5/2

Rated peak withstand current (main circuit + earthing switch, earthing connection)

kA

80, 69.6

Circuit breaker mechanical life

Next

10000

SF6 rated pressure

Rated inflation pressure (gauge pressure at 20℃)

MPa

0.12

Minimum inflation pressure (gauge pressure at 20℃)

MPa

0.08

Protection rating

—Electrical box with power supply

 

IP67

Cabinet body, cable compartment, cover plate

 

IP5X

Annual relative leakage rate of gas

%/year

≤0.01

Mechanical Operation Sequence

 

0-0.3s-CO-180s-CO

Expected service life

Year

40

Busbar/Grounding busbar (copper bar)

 

240mm2

Institutional and Secondary Operating Voltage

 

Spring mechanism AC/DC 220

Name

Unit

Isolating switch

Structural type

 

Direct-acting

Rated voltage

kV

72.5

Rated frequency

Hertz

50

Rated current

A

630/1250

Rated insulation level

Power-frequency withstand voltage (phase-to-phase, phase-to-ground)

kV

160

Power-frequency withstand voltage (isolated break)

kV

160+42

Lightning impulse withstand voltage (phase-to-phase, phase-to-ground)

kV

380

Lightning Impulse Withstand Voltage (Isolation Break)

kV

350 + 60

Short-time withstand current and duration (main circuit + earthing switch, earthing connection)

kA/s

31.5/4, 27.5/2

Rated peak withstand current (main circuit + earthing switch, earthing connection)

kA

80, 69.6

Mechanical life

Next

3000

Expected service life

Year

40

Busbar/Ground Busbar (Copper Bar)

 

240mm2

Secondary operating voltage

 

AC/DC220

Name

Unit

Grounding switch

Short-time withstand current and duration (main circuit + earthing switch, earthing connection)

kA/s

31.5/2

Rated peak withstand current (main circuit + earthing switch, earthing connection)

kA

80, 69.6

Mechanical life

Next

3000

Expected service life

Year

40

Secondary operating voltage

 

AC/DC220

Environmentally Friendly Gas-Insulated Ring Main Unit Equipment

The UN0-12, 24/630-25kA environmentally friendly gas-insulated ring main unit is a fully sealed and fully insulated ring main unit that employs advanced vacuum interrupter technology. From the design perspective, it meets environmental requirements by being oil-free and SF6-free. All conductive parts inside the switchgear are housed in a sealed stainless steel enclosure, with dry air serving as the primary insulating medium within the enclosure. The main switch uses a vacuum arc-extinguishing system, while the isolating switch features a three-position structure. The enclosure boasts an IP67 protection rating, making it immune to the effects of condensation, frost, salt spray, pollution, corrosion, ultraviolet radiation, and other similar factors.

SF6 Gas-Insulated Ring Main Unit Equipment

UN3-12, 24-1250-2500-3150-31.5kA gas-insulated ring main units are designed and manufactured in compliance with GB and IEC standards. They feature a fully insulated, hermetically sealed structure and are suitable for harsh environments such as those characterized by pollution, salt spray, humidity, and high altitudes. A variety of configurations are available to meet even more demanding requirements. <br/> Applied to <br/> 10. Offshore and onshore wind power step-up substations for 20kV voltage grid integration <br/> 10. Offshore and onshore energy storage and photovoltaic step-up substations for 20kV voltage networks <br/> · 10, 20 kV voltage-level substations for power transmission and distribution, used for voltage boosting or reducing. <br/>

SF6 Gas-Insulated Ring Main Unit Equipment

The UN3-36, 40.5-630-25-31.5 kA series gas-insulated ring main units are designed and manufactured in compliance with GB and IEC standards. They feature a fully insulated, hermetically sealed structure and are suitable for harsh environments such as those characterized by pollution, salt spray, humidity, and high altitudes. A variety of configurations are available to meet even more demanding requirements. <br/> Applied to <br/> 33. 35kV voltage-rated box-type substations for offshore and onshore wind power generation; <br/> 33. Offshore and onshore energy storage systems and photovoltaic box-type substations for 35kV voltage networks; <br/> 33. Ring main units for substations and distribution networks operating at 35 kV.

Environmentally Friendly Gas-Insulated Ring Main Unit (Spare)

The UN0-12/630A-25kA environmentally friendly gas-insulated ring main unit is a fully sealed and fully insulated ring main unit that employs advanced vacuum interrupter technology. From the design perspective, it meets environmental requirements by being oil-free and SF6-free. All conductive parts inside the switchgear are housed in a sealed stainless steel enclosure, with dry air serving as the primary insulating medium within the enclosure. The main switch uses a vacuum arc-extinguishing system, while the isolating switch features a three-position structure. The enclosure boasts an IP67 protection rating, making it immune to the effects of condensation, frost, salt spray, pollution, corrosion, ultraviolet radiation, and other similar factors.