  • 33333.jpg.png
  • yfw1y155u7gh7gin.png
  • 6shyp07h6xxo3usy.png

SF6 Gas-Insulated Ring Main Unit Equipment


UN3-12, 24-1250-2500-3150-31.5kA gas-insulated ring main units are designed and manufactured in compliance with GB and IEC standards. They feature a fully insulated, hermetically sealed structure and are suitable for harsh environments such as those characterized by pollution, salt spray, humidity, and high altitudes. A variety of configurations are available to meet even more demanding requirements.
Applied to
10. Offshore and onshore wind power step-up substations for 20kV voltage grid integration
10. Offshore and onshore energy storage and photovoltaic step-up substations for 20kV voltage networks
· 10, 20 kV voltage-level substations for power transmission and distribution, used for voltage boosting or reducing.

Classification

Product Center


▎Product Features


· This product is designed and manufactured in compliance with GB and IEC standards.
· Manufactured with a structural design featuring vacuum arc-extinguishing and all-insulated by SF6 gas;
· The enclosure’s protection rating reaches IP67, and during installation and throughout its service life, it requires no unscheduled inflation or recharging of gas.
· The product meets requirements for altitudes of 5,000 meters and below;
· Suitable for operation in environments with industrial pollution, salt spray, and high humidity; meets C3 standard on land and C4 standard at sea.


 

 

▎Operating Environment Conditions


Altitude: ≤5000m (When the operating altitude of the equipment exceeds 2000m, this must be specifically noted);
Ambient temperature: Maximum temperature +50℃, minimum temperature -50℃, average value within 24 hours ≤35℃;
Environmental humidity: Average relative humidity over 24 hours ≤ 95%; average monthly relative humidity ≤ 90%.
Electromagnetic interference: The amplitude of electromagnetic interference induced in the secondary system ≤ 1.6 kV;
Installation environment: The surrounding air contains no explosive or corrosive gases, and the installation location is free from frequent, severe vibrations or impacts.
Note: If the operating environment conditions exceed those specified above, please consult our company to arrange a custom solution.

 


▎Applicable Standards


IEC 62271-1:2017 and GB/T 11022-2020 – Common Technical Requirements for High-Voltage Switchgear and Control Equipment
IEC 62271-200:2011 and GB/T3906-2020 3.6 kV to 40.5 kV AC metal-enclosed switchgear and controlgear
IEC 62271-100:2017 and GB/T 1984-2014 — AC High-Voltage Circuit Breakers
IEC 62271-105:2021 and GB/T16926-2009 — AC High-Voltage Load Break Switch-Fuse Combination Apparatus
IEC 16271-102:2001+A1:2011 and GB/T1985-2014 — High-voltage AC isolating switches and earthing switches
IEC60529 and GB/T4208-2017: Enclosure Protection Ratings (IP Codes)
GB/T11023-2018 — Test Method for Gas Sealing of Sulfur Hexafluoride in High-Voltage Switchgear; DL/T402-2016 — Technical Specifications for Ordering High-Voltage AC Circuit Breakers
DL/T486-2021 Technical Specifications for Ordering High-Voltage AC Disconnect Switches and Earthing Switches
DL/T403-2017 12kV~40.5kV High-Voltage Vacuum Circuit Breakers — Ordering Technical Specifications
. DL/T404-2018 3.6kV~40.5kV AC Metal-Enclosed Switchgear and Control Equipment; DL/T593-2016 Common Technical Requirements for High-Voltage Switchgear and Control Equipment

 


▎Recycling and Reuse


Qian Gu Electric is committed to environmental protection. Its products have been certified under the international environmental management system I5014001 and strictly adhere to this standard.
Recycling and Disposal
The UN3 series switchgear is designed and manufactured in compliance with the national standard GB/T 3906 and the international standard IEC 62271-200. At the end of the product’s lifecycle, SF6 gas will be recovered and reused in accordance with relevant standards.
Sustainable development
The UN3 series switchgear continuously reduces the use of SF6 during manufacturing and does not use SF6 gas during installation.
All products are made from 100% recyclable materials.
Provide self-powered relays and devices to avoid additional energy consumption.

 


▎Feature Description


1. Side-mounted main busbar: Rated current meets 1250A and 2500A.
2. Independent busbar room: Meets the requirements for single-cabinet or dual-cabinet configurations.
3. Three-position disconnector and mechanism: Can be operated manually or electrically.
4. Circuit Breaker and Mechanism: The circuit breaker features a spring-operated mechanism with automatic reclosing capability, and can be manually or electrically energized.
5. Installation of Cable Accessories and Surge Arresters: C-type bushings—choose either 1 set of cable + surge arrester or 2 sets of cable + surge arrester.
6. Cable Room: Meets installation requirements for cables of various specifications.
7. Cable Room Pressure Relief Channel
8. Air box pressure relief channel
9. Circuit Breaker Room
10. In-cabinet bushing
11. Nameplate
12. Simulated busbar
13. Protective device

 


▎Technical Specifications


Operating continuity levels defined in GB/T 3906

Other high-voltage compartments or functional units remain energized.

LSC 1: Lower service continuity

 

LSC 1 LSC 2

LSC 2: Higher Service Continuity

 

 

●

Partition between compartments

PI: Insulating partition

 

PI

PM

PM: Metal Grounding Baffle

 

 

●

Insulation and Switching

Main circuit disconnection

 

 

Vacuum circuit breaker

Interrupting medium

 

 

Vacuum arc-extinguishing chamber

Insulating medium

 

 

SF6 gas

Relative inflation pressure

Rated inflation pressure (gauge pressure at 20℃)

MPa

0.04

Minimum inflation pressure (gauge pressure at 20℃)

MPa

0.02

Annual relative leakage rate of gas

 

%/year

≤0.01

Insulation level

Rated voltage

 

kV

12/24

Rated frequency

 

Hertz

50

 

Rated insulation level

Power-frequency withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter contacts)

kV

42/65

Power-frequency withstand voltage (isolated break)

kV

48/79

Power-frequency withstand voltage (auxiliary and control circuits)

kV

2

Lightning impulse withstand voltage (phase-to-phase, phase-to-ground, vacuum interrupter)

kV

75/125

Lightning Impulse Withstand Voltage (Isolation Break)

kV

85/145

Current level

Rated current—busbar

A

1250/2500/3150

Rated short-circuit breaking current

kA

31.5

Rated short-circuit making current (main switch/grounding switch)

kA

80/80

Short-time withstand current and duration (main circuit + earthing switch, earthing connection)

kA/s 31.5/4 · 27.4/2

Rated peak withstand current (main circuit + earthing switch, earthing connection)

kA

80/68

Internal arc fault withstand capability

Grade A

A FL front and side views

kA

31.5

Duration

S

0.5

Enclosure protection rating

Complies with GB/T4208 standard enclosure protection.

An energized electrical box

 

IP67

Cable Room

 

IP43

Institutional Room

 

IP4X

Low-pressure room

 

IP4X

Mechanical impact protection rating

Grade compliant with GB/T 20138

 

IK07

Other features

Expected service life

Year

30

Busbar/Grounding busbar (copper bar)

 

240 mm²

Environmentally Friendly Gas-Insulated Ring Main Unit Equipment

The UN0-12, 24/630-25kA environmentally friendly gas-insulated ring main unit is a fully sealed and fully insulated ring main unit that employs advanced vacuum interrupter technology. From the design perspective, it meets environmental requirements by being oil-free and SF6-free. All conductive parts inside the switchgear are housed in a sealed stainless steel enclosure, with dry air serving as the primary insulating medium within the enclosure. The main switch uses a vacuum arc-extinguishing system, while the isolating switch features a three-position structure. The enclosure boasts an IP67 protection rating, making it immune to the effects of condensation, frost, salt spray, pollution, corrosion, ultraviolet radiation, and other similar factors.

SF6 Gas-Insulated Ring Main Unit Equipment

UN3-12, 24-1250-2500-3150-31.5kA gas-insulated ring main units are designed and manufactured in compliance with GB and IEC standards. They feature a fully insulated, hermetically sealed structure and are suitable for harsh environments such as those characterized by pollution, salt spray, humidity, and high altitudes. A variety of configurations are available to meet even more demanding requirements. <br/> Applied to <br/> 10. Offshore and onshore wind power step-up substations for 20kV voltage grid integration <br/> 10. Offshore and onshore energy storage and photovoltaic step-up substations for 20kV voltage networks <br/> · 10, 20 kV voltage-level substations for power transmission and distribution, used for voltage boosting or reducing. <br/>

SF6 Gas-Insulated Ring Main Unit Equipment

The UN3-36, 40.5-630-25-31.5 kA series gas-insulated ring main units are designed and manufactured in compliance with GB and IEC standards. They feature a fully insulated, hermetically sealed structure and are suitable for harsh environments such as those characterized by pollution, salt spray, humidity, and high altitudes. A variety of configurations are available to meet even more demanding requirements. <br/> Applied to <br/> 33. 35kV voltage-rated box-type substations for offshore and onshore wind power generation; <br/> 33. Offshore and onshore energy storage systems and photovoltaic box-type substations for 35kV voltage networks; <br/> 33. Ring main units for substations and distribution networks operating at 35 kV.

Environmentally Friendly Gas-Insulated Ring Main Unit (Spare)

The UN0-12/630A-25kA environmentally friendly gas-insulated ring main unit is a fully sealed and fully insulated ring main unit that employs advanced vacuum interrupter technology. From the design perspective, it meets environmental requirements by being oil-free and SF6-free. All conductive parts inside the switchgear are housed in a sealed stainless steel enclosure, with dry air serving as the primary insulating medium within the enclosure. The main switch uses a vacuum arc-extinguishing system, while the isolating switch features a three-position structure. The enclosure boasts an IP67 protection rating, making it immune to the effects of condensation, frost, salt spray, pollution, corrosion, ultraviolet radiation, and other similar factors.